Sizing Technology Rooms

During the programming phase of any new construction or major renovation project, space allowances must be determined and accounted for the mechanical, electrical, plumbing and technology (MEPT) rooms. With increasing IT demands, sizing and location of the technology rooms is becoming more critical every day.

The following guidelines determined by BICSI are followed throughout the industry. BICSI is the worldwide association that establishes standards and best practices for the Information and Communications Technology (ICT) industry. These sizes are based upon providing two low-voltage jacks per 100 square feet of usable floor space throughout the building.

Table 1:Telecommunication Room (TR) Size Guidelines

Serving Area Size
Minimum Room Dimensions
≤ 5000 sq ft 10′ x 8′
< 5000 sq ft to 8000 sq ft 10′ x 9′
< 8000 sq ft to 10,000 sq ft 10′ x 11′

 

Each building typically has one main telecommunications room (MTR) and as many additional telecommunications room (TRs) as necessary. As a rule of thumb for a typical office building, the MTR should be at least 8’x12′ and each TR should be at least 8’x10′. Providing these minimum dimensions is important to maintain the clearances necessary for servicing the front and back of each equipment rack. Exposed ceilings are preferred to permit maximum flexibility and accessibility, and a 10′ clear height is desirable.

Figure1: Telecommunication Room image

Figure 1: Telecommunications Room (TR) Layout

The number of devices being placed on the network is constantly increasing. Research estimates that more than 30 billion devices will be connected to the Internet of Everything by 2020. Using typical copper network architecture, this means that significant spare capacity needs to be provided as the size of the technology rooms will continue to grow.

Locating Technology Rooms

The data cable (e.g., Cat-6) from the TR to the work area outlet (i.e., the jack in the wall) shall not exceed 90m (295 ft). When accounting for pathway routes and vertical runs, vertical runs up and down walls and service loops, this distance on the drawings is actually much less than 295 feet. As a result, a good rule of thumb is that every point in the building should be within a 200 ft radius of a TR.

Figure 2: TR Serving Area Radius image

Figure 2: TR Serving Area Radius

Technology equipment and the cabling needed for it is rapidly changing. Providing Technology Rooms that are properly located and sized is very important to “future-proof” buildings for the next big thing. Considering Apple now has a watch, you never know what the next big thing will be.

 

Headshot of Justin Schultz  

About the Author

JUSTIN SCHULTZ, PE, RCDD, LEED AP ID+C
Justin has 12 years of electrical engineering design experience, including 7 years of technology design. He is an RCDD (Registered Communications Distribution Designer).
line spacer
Meet the other members of Korda Engineering’s
Technology Department
line spacer
Headshot of Stan Kmonk
STANLEY KMONK, PE, RCDD, LEED AP BD+C
Stan is the head of Korda’s electrical department. He has over 35 years of experience and oversees the technology department.
line spacer
Headshot of Mark King
MARK KING, RCDD
Mark has been a technology design consultant for nearly 20 years. He is a member of the BICSI Standards committee and has co-chaired or participated in multiple best practice sub-committees.
line spacer